Signal Conditioning Module DI-8B33

Levertijd:
3~4 weken
SKU
DI-8B33

DI-8B33 Isolated True RMS Input Module (100 mV ~ 300 V RMS Input Range)

● Interfaces RMS Voltage (100 mV to 300 V)
● Designed For Standard Operation With Frequencies of 45 Hz ~ 1 kHz (Extended Range to 20 kHz)
● Compatible With Standard Current and Potential Transformers
● ±0.25% Factory Calibrated Accuracy (Accuracy Class 0.2)
● 1500 Vrms Continuous Transformer Based Isolation
● Input Overload Protected to 480 V Max (Peak AC and DC) or 10A RMS Continuous
● ANSI/IEEE C37.90.1-1989 Transient Protection

DI-8B modules are an optimal solution for monitoring real-world process signals and providing high level signals to a data acquisition system. Each DI-8B33 module isolates, filters and amplifies a True RMS input signal and provides an analog voltage output. Signal filtering is accomplished with a three-pole filter optimized for time and frequency response which provides 70dB of normal-mode-rejection at 60Hz. One pole of this filter is on the field side of the isolation barrier for anti-aliasing, and the other two are on the system side. A special input circuit on the DI-8B33 module provides protection against accidental connection of power-line voltages up to 30VAC. Isolation is provided by optical coupling to suppress transmission of common mode spikes or surges. The module is powered from +5VDC, ±5%. The modules are designed for installation in Class I, Division 2 hazardous locations and have a high level of immunity to environmental noise.
Meer informatie
Art.nr.
DI-8B33
Fabrikant
Dataq Instruments
Land van herkomst
Verenigde Staten
Input Range
0mV to 100mV (DI-8B33-01)
0V to 1V (DI-8B33-02)
0V to 10V (DI-8B33-03)
0V to 150V (DI-8B33-04)
0V to 300V (DI-8B33-05)
Output Range
0 to +5V
Algemeen
Input Frequency Range
Normal 45Hz to 1KHz
Extended 1KHz to 10KHz
Impedance
499 KΩ ± 1 (DB-8B33-01 & DB-8B33-02)
1 MΩ ± 1% (DB-8B33-03, DB-8B33-04, DB-8B33-05)
.05 Ω (DB-8B33-06)
Input Protection
Continuous 300Vrms (DB-8B33-01 - DB-8B33-05)
2Arms (DB-8B33-06)
Transient ANSI/IEEE C37.90.1 (DB-8B33-01 - DB-8B33-05)
** (DB-8B33-06)
CMV, Input to Output, Input to Power 1500Vrms max
Transient, Input to Output, Input to
Powe
ANSI/IEEE C37.90.1
CMR (50Hz or 60Hz) 120dB
Accuracy*
Sinusoid
50/60Hz ±0.15% Span
45Hz to 1KHz ±0.25% Span
1KHz to 10KHz (DB-8B33-02 ~ 05) ±1% Sp
1KHz to 10KHz (DB-8B33-01, DB-8B33-06) ±3% Span
Non-Sinusoid
Crest Factor = 1 ±0.15% Span
Crest Factor = 2 ±0.20% Span
Crest Factor = 3 ±0.25% Span
Crest Factor = 4 ±0.45% Span
Vs. Temperature ±100ppm/°C
Response Time, 99% Span <400ms
Output Voltage Limit ± 9V
Output Ripple and Noise 0.0375% Span rms
Output Protection (Transient) ANSI/IEEE C37.90.1 (Continuous Short to Ground)
Power Supply Voltage +5VDC ±5%
Power Supply Current 30mA
Power Supply Sensitivity ±200ppm/%
Dimensions 28.1 x 41.9 x 10.2mm
Operating Temperature -40ºC to +85ºC
Storage Temperature -40ºC to +85ºC
Humidity 0 to 90% Noncondensing
*Includes nonlinearity, hysteresis and repeatability.
**For 1 to 25 seconds the max allowable transient current rating is √2500/(event time). For less than 1 second, ANSI/IEEE C37.90.1 applies with a 0.05 Ω load. For greater than 25 seconds, the 2 Arms continuous rating applies.